Posioning
Ensure metallic objects have not been posioned close to the emier pins of
the ioniser during installaon. This will aect its performance.
Reducing the output voltage for example from 7500V to 4000V and not
reseng the ion level would aect the calibraon causing the controller to
alarm repeatedly aer a short period.
BarMaster Diagnoscs
Ensure the ioniser is clean, set the output voltage to the correct level for the
ioniser. The ion level on the BarMaster or SmartControl Touch display should
produce a %.
a. If Ion level is 0% ioniser is faulty.
b. If 10-34% with a 35% alarm seng, see the cleaning secon
If aer cleaning a 80-99% Ion level is reached, you can then adjust the output
voltage to suit required ioniser. Only then can you reset the Ion Ref.
If the Ion level is well below the alarm level % of the Ion output, it will shut
down and a solid red LED will show.
Should the solid red LED persist, connect your BarMaster and follow the
Troubleshoong secon or contact your local Meech distributor.
Using a high voltage probe (RS 610 281) and meter (RS 610 590) can be used
to measure the voltage output of the ionisers. The voltage output will vary to
the ioniser connected to the 233v4. Please see corresponding manual.
WARNING
Only reset the Ion Reference with the ioniser connected and clean. Failure
to do so will result in an incorrect calibraon.