4.2. Running a test
4.2.1. VT/PT test
In this section, an example of running a test using the following
configuration (see § 4.3 for how to configure the instrument) is shown:
Set Date/Time: July 4, 2010. 6:00 PM
Set values in Nameplate:
Primary Voltage:19920; Secondary Voltage: 7200
Select Type: VT/PT
Select Test Mode: CONT/Ratio
Storage Mode: Manual
Set Filter: Normal
Set Language: English
- Typical Connection
RATIO 2.767 : 1
PRIMARY SECONDARY
19920:7200CT
H RED
H BLACK
X BLACK
X RED
X RED
X BLACK
H BLACK
H RED
Alternate Connection
RATIO 1.383 : 1
32