31
Display: Alpha numeric LCD (130 mm x 35 mm) giving test information and a large
(20 mm) 3
1
2 digitLCD, maximum reading 1999
Instrument Protection: Meets the general requirements of IP54
Temperature Effect: <±0,1%/°C over the temperature range -10°C to +40°C
Temperature Range: Operating: -10°C to +40 °C
Storage: -20°C to +60°C
Humidity: Operating: 90% RH max. at 40°C
Flash Test: 3 kV a.c.
Voltage Withstand: In the event of a system fault the instrument will withstand 240 V a.c.
applied between any two terminals.
Compliance with Standards: BS 7430 (1992) BS7671 (1992) NFC 15-100
VDE 0413 Part 7 (1982) IEC364
Power Supply: (i) Internal rechargeable sealed lead acid cells 12 V nominal, 2,6 Ah
capacity. Battery voltage range over which basic accuracy is
maintained, 11,0 V to 13,5 V.
Battery life: Typically 5 Hours continuous use
Battery charging time: 6 hours max. (from completely exhausted).
Charging supply required: 100 V to 130 V or 200 V to 260 V a.c. 50 Hz/60 Hz.
Power consumption: 25 VA