AVTM24-1J REV A April 2006
10
Battery
Charger:
Separate charger unit plugs into
receptacle on measuring unit. Full
charge in 14 hours. Charging may be
continued while instrument is
operating. Fused, with UL listed 3-
wire line cord and plug. Power
requirements, 0.22 amps at 115 volts,
50/60 Hz; or 0.165 amps at 230 volts,
50/60 Hz.
Fuse ratings:
115V-0.2A Slow Blow
230V-0.1A Slow Blow
CONTINUOUS OPERATING
TIME BETWEEN CHARGES
CONTINUOUS OPERATING TIME
WHILE ON CHARGE
RANGE
MEASURING
CIRCUIT
BATTERY
DISPLAY
BATTERY
MEASURING
CIRCUIT BATTERY
DISPLAY
BATTERY
6 mO 1 Hour 15 Hours 1 Hour No Limit
60 mO 10 Hours 15 Hours No Limit No Limit
600 mO 100 Hours 15 Hours No Limit No Limit
6 O 1000 Hours 15 Hours No Limit No Limit
60 O 1000 Hours 15 Hours No Limit No Limit
Battery Life: Approximately 300 full charge-
discharge cycles.