EasyManuals Logo

Megger MFT1700 series User Manual

Megger MFT1700 series
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
39
Voltage:
Intrinsic accuracy: ±2% ±1 V
EN61557-1 Range: 10 V to 600 V
Phase rotation indication.
Max service error: ±5% ±2 digits
Frequency:
Intrinsic accuracy: ±0.5% ±2 digits
Resolution: 0.1 Hz
EN61557 Range: 15 Hz to 400 Hz
Max service error: ±5% ±3 digits
Earth Test Ranges:
Intrinsic accuracy: ±2.0% ±3 digits
ART method ±5.0% ±3 digits
Stakeless method ±7.0% ±3 digits
Resolution: 0.01 Ω
EN61557 range: 1.0 Ω to 1.99 kΩ
Current: 0.45 mA or 4.5 mA.
Noise rejection: 20 V pk/pk (7 V rms)
Max probe resistances: Rp, Rc = 100 kΩ @ 50 V
Max service error: ±20% ±3 digits
Current (via Clamp meter):
Intrinsic accuracy: ±5.0% ±3 digits
Resolution: 0.1 mA
EN61557 Range: 0.5 mA – 199 A
Max service error: ±10% ±2 digits
mV Sensor input (1730)
including temperature (third party module)
±1.0% ±2 digits
Range 0.0 mV to ±199.9 mV dc
Resolution 0.1 mV
Internal memory (MFT1835)
Capacity 1000 results
Bluetooth communication
Power consumption:
Nominal minimum: 60 mA (Voltage range with no input voltage)
Nominal maximum: 350 mA (Active Insulation test set to 1000 V / 1 MΩ)
Range: -20 °C to +55 °C
Temperature (via 3rd Party Module):
Intrinsic accuracy: ±1.0% ±2 digits
Resolution: 1 °C
Range: -20 °C to +100 °C

Table of Contents

Other manuals for Megger MFT1700 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Megger MFT1700 series and is the answer not in the manual?

Megger MFT1700 series Specifications

General IconGeneral
BrandMegger
ModelMFT1700 series
CategoryTest Equipment
LanguageEnglish

Related product manuals