60 
 
Fault 
code 
Fault type  Possible fault cause  Solutions 
Er.oH1 
Inverter module 
heatsink 
over-temperature 
The ambient temperature is too high.  Lower the ambient temperature 
The duct is blocked.  Clean the duct 
The fan is damaged.  Replace the fan 
The inverter module is abnormal.  Seek for service support 
Er.oH2 
Rectifier heatsink 
over-temperature 
The ambient temperature is too high.  Lower the ambient temperature 
The duct is blocked.  Clean the duct 
The fan is damaged.  Replace the fan 
Er.oL1 Drive overload 
The motor parameters are incorrect.  Perform the parameter auto-tuning of the motor 
The load is too large.  Adopt the drive with higher power 
The DC braking amount is too large. 
Reduce the DC braking current and lengthen the 
braking time 
When instantaneous stop happens, 
restart the rotating motor 
Set the start mode P08.00 as the speed tracking 
restart function 
The acceleration time is too short.  Lengthen the acceleration time 
The grid voltage is too low.  Check the grid voltage   
V/F curve is improper.  Adjust V/F curve and torque increase 
Er.oL2 Motor overload 
The motor overload protection factor 
setting is incorrect. 
Set the overload protection factor of motor correctly. 
The motor is blocked or the sudden 
change of load is too large. 
Check the load 
The universal motor runs at low speed 
for a long time, with heavy load. 
If long-term low-speed running is required, special 
motor should be used. 
The grid voltage is too low.  Check the grid voltage   
V/F curve is improper.  Set V/F curve and torque increase correctly 
Er.EFT 
Emergency stop   
or external 
device fault 
Stop suddenly by pressing the STOP 
key 
See the function definition of the STOP key in 
P00.04 
External fault emergency-stop terminal 
is enabled. 
After the external fault is revoked, release the 
external fault terminal 
Er.EEP 
EEPROM 
read/write  
fault 
The read/write error of the control 
parameters occurs. 
Reset by pressing the STOP/RESET key, seek for 
service support