EasyManua.ls Logo

MGC INX-10A Series - 6.4.5 Two Stage with Basic Reporting and Power Supply Output Addressing

MGC INX-10A Series
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65
Configuration
6.4.5 Two Stage with Basic Reporting and Power Supply Output Addressing
In order to maximize the amount of addresses available, if a NAC circuit is configured as a
Power Supply, the next configured NAC Circuit is assigned the address reserved for the
previous Circuit.
Example Application
NAC 5 configured as a Power Supply.
INX-10A Common Trouble reporting address is 190.
To configure the recommended base address
To configure the INX for Two Stage with Basic Reporting in a Mircom system
To configure the INX for Single Stage with Basic Reporting in a Secutron system
To configure NAC 5 as a Continuous Power Supply
Set DIP switch SW1 as: 0-1-0-1-1-0-1-0
OFF-ON-OFF-ON-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-0-1-0
OFF-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-1-1-0
OFF-ON-ON-OFF
Set DIP switch SW4-7 and SW4-8 as: 1-0
ON-OFF
Attention: If NACs are configured the Evacuation Rate must be set on SW2 4-6. For
more information see Setting Alert Rates, Evacuation Rates, NAC 5
Output Functions on page 42.
Table 16 Assigning Addresses - Two Stage Application, 1 Power Supply Output
Function Address Recommended
Device Address
Common Trouble Base Address 90
Signal Silence Base Address + 1 91
Activate NAC1, return NAC1 line status Base Address + 2 92
Activate NAC2, return NAC2 line status Base Address + 3 93
SW1
1
8
234567
SW2
ON
1
8
234567
SW2
ON
1
8
234567
SW4
ON
1
8
234567
!

Table of Contents