EasyManua.ls Logo

MGC INX-10A Series - 10.0 Appendix B - Power Supply & Battery Calculations

MGC INX-10A Series
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
97
Appendix A - Specifications And Features
10.0 Appendix B - Power Supply & Battery
Calculations
Use the form below to determine the required Main Chassis and Secondary Power Supply (batteries).
Total Current Requirement
ALARM (B)______ Amps.
Battery Capacity Requirement
([STANDBY (A)______ ] X [(24 or 60 Hours)___ ]) + ([ALARM (B)______ ] X [*Alarm in Hr.] _____) =
(C)______AH
Battery Selection
Multiply (C) by 1.20 to derate battery.
Batteries BA-104(4AH), BA-1065(7AH) and BA-110(12AH) will fit into the INX-10A, BA-117 (18 Ah) fit in the
INX-10ADS only
*Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous power without provision of any
disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local
codes. Refer to9.0 Appendix A - Specifications And Features for specifications.
Power Requirements (All currents are in amperes)
Model Number Description Qty Standby
Total
Standby
Alarm
Total
Alarm
INX-10A Main Chassis (10 Amp) X 0.200 = 0.350 =
INX-10ADS Chassis (10 Amp) X 0.200 = 0.350 =
INX-10AC Chassis (10 Amp) X 0.200 = 0.350 =
Signal Load (bells, horns, strobes, and etc.) X
=
Auxiliary Power Supply =
Alarm
=
Total currents (Add above currents) STANDBY (A)(B)

Table of Contents