Output power rating
AC-input
Voltage
Frequency
Power factor
Output specification
Voltage
Frequency
Harmonic distortion
Overload capability
Battery (sealed lead-acid,
maintenance free)
Environmental and safety
Noise level
Operating temperature
Relative humidity
Safety
EMC
Agency markings
< 50 dBA
0 to 40° C
20 to 90% (without condensation)
UL 1778 / cUL CSA 22.2 N°107.1
FCC 47 CFR Part 15, class A
UL, CSA
6 x 12 V - 9 Ah
6 x 12 V - 7 Ah
Single phase, 60 V / 70 V / 80 V to 142 V
(1)
50/60 Hz (auto-select)
≥ 0.95
Pulsar EX 3200RT
3200 VA / 2080 W
Pulsar EX 2200RT
2200 VA / 1540 W
3400753300/AE - Page 25
(1) Input voltage correspond to 33% / 66% / 100% of the nominal power rating.
(2) Adjustable from 100 V to 127 V using UPS Driver software.
(3) Frequency converter mode may be set using the UPS Driver software.
6.1 Technical characteristics
6. Appendices
Single phase, 120 V ± 3%
(2)
50/60 Hz ± 0.5%
(3)
< 4% on linear load, < 6% on non linear load
110% continuous, 130% 12s, > 130% 1.5s
Pulsar EXB
2200/3200 RT
72VDC - 18 Ah
Runtime @ full load
20min -40min -60min -80min
1EXB -2EXB -3EXB -4EXB
QUALITY
Designed, Manufactured and
marked under ISO 9001 quali-
ty system.
UL, CSA
FCC Class A
UL , cUL
AC INPUT
BATTERY
AC OUTPUT
AC/DC PFC
CONVERTER
DC/AC
INVERTER
DC/DC
PUSH PULL
POWER
SUPPLY
EMI FILTER EMI FILTER
SAFETY
RELAY
BYPASS
RELAY
BATTERY
CHARGER