EasyManua.ls Logo

Micropack FDS303 - 0-20 Ma Output

Micropack FDS303
37 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
FDS303 Safety and Technical Manual
Rev: 1.7 ECN: 4535 Ref: 3303.0001
FDS303 Flame Detector
This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2018
3.3.1 0-20mA Output
The following wiring connection diagram shows correct wiring of the detector when a 0-20mA
output is required.
Figure 5: 3 Wire Termination
Factory Fixed Values
Current Output
Event
0mA
Power/Detector Fault
1.5mA
Optical Fault
4mA
Healthy
18mA
Alarm
21mA
Over-range
Note:
The tolerance on the above outputs is +/- 0.3 mA dc current with a maximum loop
resistance of 500 ohms