FDS303 Safety and Technical Manual
Rev: 1.7 ECN: 4535 Ref: 3303.0001
FDS303 Flame Detector
This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2018
6.2 Functional Testing
The detector can be function tested using the FS30x Flame Simulator, which has been specifically
designed to provide a convenient means of field testing the detector. Refer to the FS30x Flame
Simulator user manual for instructions on its use.
In the unlikely event of the detector failing to respond to the FS30x flame simulator please contact
Micropack (Engineering) Limited (info@micropack.co.uk
). Please ensure that the flame detector
and flame simulator are being used correctly in the first instance by referring to their manuals
Detector/simulator returns along with a written statement describing any fault should be sent
to the address listed below:
17
De-isolate the detector and ensure the status LED indicates green.
Reinstate the detector back into service. Check the mA output is indicating