EasyManua.ls Logo

Micropack FDS303 - 3.3 Wiring Procedure

Micropack FDS303
37 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
FDS303 Safety and Technical Manual
Rev: 1.7 ECN: 4535 Ref: 3303.0001
FDS303 Flame Detector
This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2018
3.3 Wiring Procedure
The wiring terminals are in the rear section of the detector enclosure and are accessible by
removal of the end cap.
The front section of the enclosure should only be accessed by trained personnel.
The terminal schematic detailed below shows the view looking inside the detector following
removal of the end cap.
Figure 4: Terminal Schematic
The detector has two types of alarm output available simultaneously
0-20mA (source non-isolated)
Relay (Alarm & Fault)
Listed below are wiring options dependent on the functional requirements of the detector.