R410A All DC Inverter Mini VRF MCAC-VTSM-2014-10
88 Troubleshooting
7.8 EA/E7: Fan error in A region last for more than 5 minutes in heating mode
(EA is for 8/105 model, E7 is for 120~160 model)
System faulty that T3 pipe temperature exceeds 27
degrees for more than 5 minutes when heating mode.
Whether the outdoor ambient temperature is higher than
the unit’s operating condition when heating mode.
Belongs to system
normal protection
Check whether the refrigerant volume of the system is
added according to the requirement and check if the
refrigerant leaks.
Connect the pipe again,
check leakage, insure the
pressure & add the
refrigerant.
Check whether the condenser is
blocked.
Check whether the resistance of condenser
temperature sensor is correct.
Replace temperature sensor