MCAC-VTSM-2014-10 R410A All DC Inverter Mini VRF
Troubleshooting 89
7.9 P1: High pressure protection (for all models)
Whether the wiring is correct.
Whether the wire body is broken.
Short-circuit high pressure switch. Check whether the
system can operate normally.
Replace the high pressure
switch.
Check whether the cooling system operates normally.
Whether high pressure of the system is too high.
Whether side air duct of outdoor unit meets the standard.
Whether the heat exchanger needs cleaning.
Whether the pipeline is blocked.
Whether the throttle part is stuck, stocked or works
abnormally.
Change throttle parts to
clean the blockages.