EasyManuals Logo

Midea MV6-R450WV2GN1 Service Manual

Midea MV6-R450WV2GN1
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
V6R VRF 50/60Hz
102
Midea
V6R
Series Service Manual
2.12 H0: Communication error between main board and compressor drive board
Digital display output
Description
H0 indicates a communication error between main board and compressor drive board.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Main control board and inverter driver board cannot communication for 2 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes
Loosened communication wiring from the outdoor main PCB to the inverter module.
Filter board damaged.
Compressor inverter module damaged.
Outdoor main PCB damaged.

Table of Contents

Other manuals for Midea MV6-R450WV2GN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV6-R450WV2GN1 and is the answer not in the manual?

Midea MV6-R450WV2GN1 Specifications

General IconGeneral
BrandMidea
ModelMV6-R450WV2GN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals