V6R VRF 50/60Hz
159
3.9 F7: Main power off (for MS01)
Digital display output
Description
Main power off.
All units stop running.
Error code is displayed on the malfunction MS box.
The indoor unit display board or wired controller connected to this MS displays "F8”.
Trigger / recover condition
Trigger condition: MS main power off, and UPS power is ON.
Recover condition: MS main power on, and UPS power is OFF.
Reset method: Resume automatically.
Possible causes
Abnormal power supply.
The power supply wiring is loose.
MS PCB damaged.
Procedure
F7
Main power supply shut off.
Yes
Provide normal power supply.
No
The power supply wiring is loose.
Yes
Ensure the wires are connected properly.
No
Replace the MS main PCB