2.20 P2, H5: Suction pipe low pressure protection
Description
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition:
For P2 protection: Suction pressure < 0.07MPa.
For H5 protection: P2 protection appears three times in 60 minutes.
Recover condition:
Cooling Only/Main Cooling Discharge pressure ≥ 0.23MPa and Restart permission=ON.
Heating Only/Main Heating Discharge pressure ≥ 0.18MPa and Restart permission=ON.
Reset method:
For P2 protection: Resume automatically.
For H5 protection: Manually restart.
Possible causes
Outdoor unit stop valves are closed.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Outdoor main PCB damaged.