EasyManuals Logo

Midea MV6-R450WV2GN1 Service Manual

Midea MV6-R450WV2GN1
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
V6R VRF 50/60Hz
87
2 Troubleshooting for Outdoor Unit
2.1 Warning
2.2 E0: Communication error between outdoor units
Digital display output
Description
Communication error between outdoor units.
All units stop running.
Error code is only displayed on the slave unit with the error.
Trigger / recover condition
Trigger condition: Slave unit cannot receive signal from master unit for 60s.
Recover condition: Slave unit can receive signal from master unit.
Reset method: Resume automatically.
Possible causes
Incorrect outdoor unit address setting.
Communication wires between outdoor units not connected properly.
Loosened wiring within electric control box.
Damaged outdoor main PCB or electric control box communication terminals block.
All electrical work must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
standards, codes, rules, regulations and other legislation that apply in a given situation).
Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.
Warning

Table of Contents

Other manuals for Midea MV6-R450WV2GN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV6-R450WV2GN1 and is the answer not in the manual?

Midea MV6-R450WV2GN1 Specifications

General IconGeneral
BrandMidea
ModelMV6-R450WV2GN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals