9.1.2 ULI Listed Compatible Two-Wire Smoke Detectors
Notes: Detectors of different models are not to be mixed in a circuit.
When using two-wire smoke detectors a zone module is required.
Table 31 ULI Two-Wire Smoke Detectors
Make Model / Base Compatibility
Identifier Head/Base
Rated Standby
Current (mA)
Maximum # of
devices per
circuit
Mircom
Bases MSB-65B, MSB-65B-4, MSB-65B-4R
MPD-65P MPD-65P 0.13 21
Apollo
Series 60A Bases 45681-200,-220,-232,-251
Series 65A Bases 45681-255,-256,-257,-258
55000-325 55000-325 0.13 21
55000-326 55000-326 0.13 21
55000-327 55000-327 0.13 21
55000-328 55000-328 0.13 21
Hochiki
DCD-135/HSC-220R HD-3/HB-72 0.035 12
DCD-135/NS6-220 HD-3/HB-3 0.035 12
DCD-190/HSC-220R HD-3/HB-72 0.035 12
DCD-190/NS4-220 HD-3/HB-3 0.035 12
DCD-190/NS6-220 HD-3/HB-3 0.035 12
SIJ-24/HSC-220R HD-3/HB-72 0.04 12
SIJ-24/NS4-220 HD-3/HB-3 0.04 12
SIJ-24/NS6-220 HD-3/HB-3 0.04 12
SLR-24/HSC-220R HD-3/HB-72 0.045 12
SLR-24/NS4-220 HD-3/HB-3 0.045 12
SLR-24/NS6-220 HD-3/HB-3 0.045 12
Sentrol-ESL
429C / (701E, 701U, 702E, 702U) S10A-S00 0.1 30
429CRT / (702E, 702RE, 702RU, 702U) S11A-S00 0.1 30
429CST / (702E, 702RE, 702RU, 702U) S11A-S00 0.1 30