This feature configures all addressable loops as Class A if enabled.
Panel Configuration/Features/Auto after hours
Auto afthrs.
[ ] Enabled
This feature allows the daytime/nighttime mode to be set automatically if enabled.
Panel Configuration/Features/General alarm timer
Gen.alm tmr
[x] Disabled
[ ] 5 min
[ ] 10 min
[ ] 15 min
[ ] 20 min
[ ] 30 min
This feature sets the value for the general alarm timer
Panel Configuration/Features/Common alarm relay operation
Com alm rly op
[ ] Both Stages
[x] Second Stage
This feature sets the operation of the common alarm for two stage system.
Panel Configuration/Features/Agency selection
Jurisdiction
[ ] ULI
[x] ULC
This feature selects the agency having jurisdiction for the panel.
PANEL CONFIGURATION/2. ADDRESS CFG.
Allows user to select up to what address a CLIP device would go. Loop Selection Prompt:
Loop number
Loop: __
User is prompted to introduce address upper limit; press the “#” key to move cursor to the left, press the “*”
key to move cursor to the right:
Reserved addr. space
size for CLIP device
for the current loop
Choose from 1-99:__
PANEL CONFIGURATION/3. DEVICE LABEL
Allows the user to edit the device label. Device Address Prompt:
Device address:
Loop: _ DevAddr:___
User is then prompted for adding a label (skipped if current label):