6. Installation 
 
 
 
   
6 - 14
 
(2)  Heat radiation countermeasures outside the control panel 
Measure the temperature at 40mm form tops of all units, and design the temperature rise so that it 
is 20°C or less against the ambient temperature. 
If the temperature rise at the temperature measurement position exceeds 20°C, consider adding a 
fan. 
 
 
40mm 
Temperature measurement position
40mm 
Side face  Back face 
 
 
 
 
 POINT 
The temperature of some units may rise locally, because air accumulates at a 
particular point. Therefore, take a temperature measurement in each unit.  
If a temperature at even one point exceeds 20°C in the temperature 
measurements, take a heat radiation countermeasure such as adding fans.