EasyManua.ls Logo

Mitsubishi Electric MELSEC-F FX3G Series - Allocation of Device Numbers to Input Numbers; Allocation Table; Restriction of Redundant Use of Input Numbers

Mitsubishi Electric MELSEC-F FX3G Series
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 Use of High-speed Counters
11.4 Allocation of Device Numbers to Input Numbers
163
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
11
High-Speed
Counters
12
Output Wiring
13
Wiring for
Various Uses
14
Test Run,
Maintenance,
Troubleshooting
15
Input/Output
Powered
Extension Units
16
Input/Output
Extension
Blocks
17
Extension
Power Supply
Unit
18
Other Extension
Units and
Options
19
Display Module
20
Terminal Block
11.4 Allocation of Device Numbers to Input Numbers
The high-speed counter numbers are allocated to the input terminals X000 to X007 as shown in the following
table. The input terminals not allocated for high-speed counters can be used as general input terminals.
11.4.1 Allocation table
U: Up-count input D: Down-count input A: A-phase input B: B-phase input
R: External reset input S: External start input
*1. When a special auxiliary relay is driven in a program, the input terminals and their associated
functions are switched.
For the function switching method, refer to Subsection 11.9.2.
11.4.2 Restriction of redundant use of input numbers
The input terminals X000 to X007 can be used for high-speed counters, input interruption, pulse catch, SPD,
ZRN and DSZR instructions and general-purpose inputs. Take care not to overlap the input numbers.
Counter type Counter No.
Input allocation
X000 X001 X002 X003 X004 X005 X006 X007
1-phase 1-count
input
C235 U/D
C236 U/D
C237 U/D
C238 U/D
C239 U/D
C240 U/D
C241 U/D R
C242 U/D R
C243 U/D R
C244 U/D R S
C245 U/D R S
1-phase 2-count
input
C246 U D
C247 U D R
C248 U D R
C248(OP)
*1
U D
C249 U D R S
C250 U D R S
2-phase 2-count
input
C251 A B
C252 A B R
C253 A B R
C253(OP)
*1
A B
C254 A B R S
C254(OP)*1
A B
C255
A B R S