186
APPX
Appendix 7 Machinery Directive
Machinery Directive related standards
Immunity requirements
Standard: EN61326-3-1:2008
*1 Safety programmable controller is an open-type device intended to be placed in a conductive control panel or similar type of enclosure.
The tests were conducted with the safety programmable controller installed in a control panel.
Test item Test description Value specified in standard
EN61000-4-2
Electrostatic discharge immunity
*1
An electrostatic discharge is applied to
the enclosure of the equipment.
8kV: Air discharge
6kV: Contact discharge
EN61000-4-3
Radiated, radio-frequency, electromagnetic field
immunity
*1
An electric field is radiated to the
product.
80% AM modulation @1kHz
80 to 1000MHz: 20V/m
1.4 to 2.0GHz: 10V/m
2.0 to 2.7GHz: 3Vm
EN61000-4-4
Fast transient burst immunity
*1
Burst noise is applied to power lines
and signal lines.
AC power: 3kV
DC power: 3kV
I/O: 2kV, Functional earth: 2kV
EN61000-4-5
Surge immunity
*1
Lightning surge is applied to power
lines and signal lines.
AC power: 2kV CM, 4kV CM
DC power: 1kV CM, 2kV CM
I/O: 2kV CM
EN61000-4-6
Conducted RF immunity
*1
High-frequency noise is applied to
power lines and signal lines.
0.15 to 80MHz,
80% AM modulation @1kHz, 10Vrms
EN61000-4-8
Power-frequency magnetic field immunity
*1
The product is immersed in the
magnetic field of an induction coil.
50/60Hz, 30A/m
EN61000-4-11
Voltage dips and interruptions immunity
*1
Power voltage is momentarily
interrupted.
0%, 1 period
0%, 250/300 periods (50/60Hz)
40%, 10/12 periods (50/60Hz)
70%, 25/30 periods (50/60Hz)
EN61000-4-29
Voltage dips and interruptions immunity
*1
Power voltage is momentarily
interrupted.
40% UT 10ms
•0% UT 20ms
EN61000-4-16
Immunity to conducted, common mode
disturbances in the frequency range 0Hz to
150kHz
*1
Low-frequency noise is applied to
power lines and signal lines.
AC power
1.5k to15kHz: 1 to 10V, 20dB/decade
15k to 150kHz: 10V
DC power
1.5k to15kHz: 1 to 10V, 20dB/decade
15k to 150kHz: 10V
DC, 16 2/3Hz, 50Hz and 60Hz: 10V (continuous mode), 100V
(short term mode (1s duration)
150Hz and 180Hz: 10V (continuous mode)
I/O
1.5k to15kHz: 1 to 10V, 20dB/decade
15k to 150kHz: 10V
DC, 16 2/3Hz, 50/60Hz: 10V continuous, 100V for a short time (1s)
150Hz and 180Hz: 10V (continuous mode)