1. OVERVIEW OF MIGRATION FROM Q17nCPUN(-T) TO RnMTCPU
1.4.5 Configuration when the MR-MV200 optical hub unit is used
The MR-MV200 can branch a single SSCNETIII/H network line in three separate directions (three
outputs per one input).
A connection example when using the MR-MV200 and the specifications are shown below.
Item Description
Input voltage [V] 21.6 to 26.4 VDC (24 VDC ± 10 %)
Consumption current [A] 0.2
Mass [kg] 0.22
Mounting method Directly mounted to the control panel or with DIN rail
Cable length [m] Up to 100
Number of optical hub units Up to 16 units/line
Number of servo amplifiers
Up to 16 axes/line
Exterior dimensions [mm] 168 (H) x 30 (W) x 100 (D)
Line topology
Cascade topology Star topology