5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.2 System to Which Multiple Safety CPUs are Connected
163
5
Checking parameter settings
Read parameters in the safety remote I/O module to check if the parameters are consistent with the set values, according to
the following procedure.
1. Display the "Parameter Processing of Slave Station" window of the safety remote I/O module to be checked.
2. Select "Parameter read" in "Method selection". Then, click the [Execution] button.
3. Visually check read values if the parameters are consistent with the set values.
Safety module validation
Validate safety modules according to the following procedure to make the parameters available with set parameters.
1. Display the "Command Execution of Slave Station" window of the safety remote I/O module to validate safety module.
2. Select "Safety module validation" in "Method selection". Then, click the [Execution] button.
3. Restart the safety remote I/O module according to checking window.
Communication between Safety CPUs
This indicates network parameter setting required for communications between Safety CPUs. This section describes both
master and local station settings at a time.
Required Settings
Set the station type, network number, and parameters of the CC-Link IE Field Network master/local module. Display the
required settings. Then, select and input parameters as shown below. Complete the input. Then, click the [Apply] button in the
lower right of the window.
Window
Displayed items
*1 Station number setting method and parameter setting can be selected by setting "Parameter Editor" and "Program". Here, set
"Parameter Editor".
Setting classifications CCIEF programmable
controller
Master (1-0)
CCIEF programmable
controller
Local (1-1)
CCIEF programmable
controller
Local (1-2)
Required
Settings
Station Type Master Station Local station Local station
Network number 1 1 1
Setting method for station
numbers
Set parameters
*1
Set parameters
*1
Set parameters
*1
Station No. 0 1 2
Parameter setting method Set parameters
*1
Set parameters
*1
Set parameters
*1