480
27 TROUBLESHOOTING
27.4 Error Code List
7E48H Request error A request was received
during parameter
communication.
PRO Wait for awhile and transmit
the request again.
7E4FH Number of device
points error
Number of access points
is incorrect.
PRO Check and correct the
transmission message from
the target device and restart
data communications.

7E50H User frame No.
designation error
A user frame No. outside
the range was designated.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
Review the frame No.

7E51H User frame
unregistration
error
An unregistered user
frame number was
designated.
PRO Perform the frame registration
beforehand.
Change the frame No. and
restart data communications.
Review the frame No.

7E52H User frame
overwrite error
An overwrite request was
issued to the frame
number which has been
already registered.
PRO Change the write destination
to an unregistered frame
number.
When overwriting, delete the
given number beforehand.
7E53H Requested frame
data error
A nonexistent command
was designated in a
subcommand.
Byte count exceeding the
number of bytes that can
be requested was
designated.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
7E54H Modification not-
allowed error
The setting change
enable/disable setting is
set to be disabled.
PRO Set the setting change enable/
disable setting to 'Enable'.

7E55H User frame data
error
The user frame variable
data has an error.
PRO Check and correct the
transmission message from
the target device and restart
data communications.

7E57H Flash ROM write
error
Writing to the flash ROM
was not performed
normally.
Rewrite the module extended
parameter to the CPU module
or C24.
If the error occurs after
rewriting, replace the module.

Power is turned OFF
during writing to Flash
ROM.
CHn
ERR.
7E58H Mode
modification error
At the time of mode
modification, the mode
No. or transmission
specifications are
incorrect.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
Review the parameter
settings.

7E59H Number of writing
to flash ROM
e
xceeded error
Writing to flash ROM has
been performed 1000
times since the power was
turned ON.
Writing to flash ROM has
been performed 100,000
times.
CHn
ERR.
Review the program.
Write "0" to the flash ROM
write count area (address:
2401H) and restart data
communication.
When the number of writes
reached 100,000, replace the
module.

7E5EH PLC CPU
monitoring
function
registration error
The programmable
controller CPU monitoring
function is registered for
the communication
protocol that does not
support the function.
CHn
ERR.
Correct the communication
protocol setting.

Error code
(hexadecima
l)
Error Description Signal
name
Corrective action Protocol
MC Nonpr
ocedu
ral
Bidire
ctiona
l
Prede
fined