27 TROUBLESHOOTING
27.4 Error Code List
481
27
7E60H Device monitoring
duplicate
registration error
Programmable controller
CPU monitoring
registration was
performed twice.
Cancel the programmable
controller CPU monitoring and
perform the programmable
controller CPU monitoring
registration again.

7E61H Cycle time units
range error
The setting value for the
cycle time units is out of
range.
Correct the cycle time units
setting value.

7E62H PLC CPU
monitoring
function error
The setting value for the
programmable controller
CPU monitoring function
is out of range.
Correct the programmable
controller CPU monitoring
function setting value.

7E63H Transmission
method setting
error
The transmission method
setting for programmable
controller CPU monitoring
is incorrect.
Correct the transmission
method setting value.

7E64H Registration point
range error
The total number of word
blocks and bit blocks
registered for
programmable controller
CPU monitoring is out of
range.
Correct the setting value so
that the total number of
registered word blocks and bit
blocks is within 1 to 10.

7E66H Monitoring
condition error of
monitoring device
The monitoring condition
is out of range.
Correct the monitoring
condition.

7E67H CPU error
monitoring setting
value error
The setting value (fixed
value) for CPU error
monitoring is out of range.
Correct the setting value
(fixed) for CPU error
monitoring.

7E68H Transmission
condition range
error of
monitoring device
The setting value for the
transmission condition
(condition match send) is
out of range.
Correct the setting value for
the transmission condition
(condition match send).

7E69H CPU error
monitoring setting
value error
The setting value (fixed
value) for CPU error
monitoring is out of range.
Correct the setting value
(fixed) for CPU error
monitoring.

7E6AH Monitoring device
read point range
error
The read point of the
monitoring device is out of
range.
Correct the setting value for
the monitoring device read
point.

7E6BH to
7E6DH
CPU error
monitoring setting
valu
e error
The setting value (fixed
value) for CPU error
monitoring is out of range.
Correct the setting value
(fixed) for CPU error
monitoring.

7E6FH Modem
connection error
Modem is connected to an
incorrect channel.
Correct the destination to
which data is sent with the
modem function.

7E70H CPU error The communication with
the CPU module was not
performed normally.
C/N If the CPU module side has an
error, remove the error and
restart data communications.

7E71H System error The operating system of
C24 detected some error.
Page 490 Corrective actions
for system error
7EC1H to
7EC2H
System error The operating system of
C24 detected some error.
Page 490 Corrective actions
for system error
7EC3H Double send
request error
A send request was sent
again during processing of
the send request.
Provide an interlock for send
requests.

Error code
(hexadecima
l)
Error Description Signal
name
Corrective action Protocol
MC Nonpr
ocedu
ral
Bidire
ctiona
l
Prede
fined