EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-RJ71C24-R4 - Page 507

Mitsubishi Electric MELSEC iQ-RJ71C24-R4
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDICES APPENDIX
Appendix 3 Buffer Memory
505
A
590
(24EH)
For confirmation
of test mode
status
Test mode setting status
0000H: No specification
0001H: Hardware Tests
0002H: Self-loopback test
Depend
s on
paramet
er
setting.
R
591
(24FH)
For confirmation
of station
number setting
status
Station number (instruction setting)
(0 to 31)
Depend
s on
module
status.
R Page 445 Intelligent
function module
monitor
592
(250H)
608
(260H)
For confirmation
of transmission
control status
Communication protocol status (parameter
setting)
0: MELSOFT Connection
1: MC protocol (Format 1)
2: MC protocol (Format 2)
3: MC protocol (Format 3)
4: MC protocol (Format 4)
5: MC protocol (Format 5)
6: Nonprocedural protocol
7: Bidirectional protocol
8: (For interlink operation)
9: Predefined protocol
Depend
s on
paramet
er
setting.
Address
Dec (Hex)
Purpose Name Defaul
t value
Protocol Reference
CH1 CH2 MC Non Bi Pd