3 REPLACEMENT OF I/O MODULE
3 - 66
Noise immunity IEC801-4: 1kV
• By noise simulator of 1500Vp-p
noise voltage, 1s noise width,
and 25 to 60Hz noise frequency
• First transient noise IEC61000-4-
4: 1kV
Current consumption 0.12A (typ. all points on) 0.43A (typ. all points on)
Review the current capacity since
the current consumption is
increased.
External dimensions 130(H)34.5(W)93.6(D)mm 98(H)27.4(W)90(D)mm Wiring space is narrower.
Weight 0.25kg 0.22kg
Specifications A1SY14EU QY10
Compat-
ibility
Precautions for replacement