3 REPLACEMENT OF I/O MODULE
3 - 67
(4) Specifications comparison between A1SY18A and QY18A
: Compatible, : Partially changed, : Incompatible
Specifications A1SY18A QY18A
Compat-
ibility
Precautions for replacement
Number of output points
8 points
(16 points occupied)
8 points
(16 points occupied)
Isolation method Photocoupler Relay
The isolation method differs, but
the performance is the
equivalent.
Rated switching voltage/
current
24VDC 2A (resistance load)/point
240VAC 2A (COS=1)/point
8A/module
24VDC 2A (resistance load)/point
240VAC 2A (COS=1)/point
8A/module
Minimum switching load 5VDC 1mA 5VDC 1mA
Maximum switching
voltage
264VAC 125VDC 264VAC 125VDC
Response
time
Off on 10ms or less 10ms or less
On off 12ms or less 12ms or less
Life
Mechanical 20 million times or more 20 million times or more
Electrical
Rated switching voltage/current load
200,000 times or more
Rated switching voltage/current load
100,000 times or more
Replace the module more
frequently because the life cycle
is reduced by approximately half.
200VAC 1.5A, 240VAC 1A
(COS=0.7) 200,000 times or more
200VAC
0.75
A, 240VAC 0.5A
(COS=0.35) 200,000 times or more
24VDC 1A, 100VDC 0.1A
(L/R=7ms) 200,000 times or more
200VAC 1.5A, 240VAC 1A
(COS=0.7) 100,000 times or more
200VAC 0.4A, 240VAC 0.3A
(COS=0.7) 300,000 times or more
200VAC 1A, 240VAC 0.5A
(COS=0.35) 100,000 times or more
200VAC 0.3A, 240VAC 0.15A
(COS=0.35) 300,000 times or more
24VDC 1A, 100VDC 0.1A
(L/R=7ms )100,000 times or more
24VDC 0.3A, 100VDC 0.03A
(L/R=7ms) 300,000 times or more
Maximum switching
frequency
3600 times/hr 3600 times/hr
Surge suppressor None None -
Common terminal
arrangement
All points independent common All points independent common
Operation indication On indication (LED) On indication (LED)
Fuse None None -
External
power
supply
Voltage
24VDC±10%
Ripple voltage 4Vp-p or less
-
An external power supply is not
required.
Current
75mA
(typ. 24VDC, all points on)
-
External connection
system
20-point terminal block connector
(M3.57 screws)
18-point terminal block
(M36 screws)
Wiring change is required.
Applicable wire size
0.75 to 1.25mm
2
Core: 0.3 to 0.75mm
2
(outside diameter: 2.8mm or less)
Applicable solderless
terminal
R1.25-3.5, R2-3.5,
RAV1.25-3.5, RAV2-3.5
R1.25-3
(Sleeved solderless terminal cannot
be used.)
Current consumption 0.24A (typ. all points on) 0.24A (typ. all points on)
External dimensions 130(H)34.5(W)93.6(D)mm 98(H)27.4(W)90(D)mm Wiring space is narrower.
Weight 0.25kg 0.22kg