3 REPLACEMENT OF I/O MODULE
3 - 10
Output module
A1SY10
A1SY10EU
QY10
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
(However, the contact life span of the A1SY10EU is reduced to half.)
5) Function: not changed
A1SY14EU QY10
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
(However, contact life span is reduced to half.)
5) Function: not changed
A1SY18A QY18A
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
(However, contact life span is reduced to half.)
5) Function: not changed
A1SY18AEU QY18A
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
(However, contact life span is reduced to half.)
5) Function: not changed
A1SY22 QY22
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (no fuse)
A1SY28A (None)
Consider replacing with the QY40P + FA-TH16YSR20S
*
.
* FA-TH16YSR20S is one of the FA goods manufactured by Mitsubishi Electric
Engineering Co., Ltd.
A1SY28EU (None)
A1SY40 QY40P
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (fuse ï‚® overheat, overload protection)
AnS/QnAS series model Q series alternative model
Product Model Model Remarks (restrictions)