3 REPLACEMENT OF I/O MODULE
3 - 11
Output module
A1SY40P QY40P
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: not changed
A1SY41 QY41P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (fuse ï‚® overheat, overload protection)
A1SY41P QY41P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: not changed
A1SY42 QY42P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (fuse ï‚® overheat, overload protection)
A1SY42P QY42P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: not changed
A1SY50 QY50
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: not changed
A1SY60 QY68A
1) External wiring: changed
2) Number of slots: changed (2 modules are required.)
3) Program
Number of occupied I/O points: changed (16 points ï‚® 32 points (16 points ï‚´ 2
modules))
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (no fuse, independent common)
A1SY60E QY68A
1) External wiring: changed
2) Number of slots: changed (2 modules are required.)
3) Program
Number of occupied I/O points: changed (16 points ï‚® 32 points (16 points ï‚´ 2
modules))
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (no fuse, independent common)
AnS/QnAS series model Q series alternative model
Product Model Model Remarks (restrictions)