3 REPLACEMENT OF I/O MODULE
3 - 12
Output module
A1SY68A QY68A
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: changed (48VDC is not applicable.)
Rate output current: not changed
5) Function: not changed
A1SY71 QY71
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: not changed
A1SY80 QY80
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: changed
5) Function: not changed
A1SY81 QY81P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (fuse ï‚® overheat, overload protection)
A1SY81EP QY81P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: not changed
A1SY82 QY82P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (fuse ï‚® overheat, overload protection)
AnS/QnAS series model Q series alternative model