3 REPLACEMENT OF I/O MODULE
3 - 13
I/O module
A1SH42 QH42P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
(input part)
Rated input voltage: changed (12VDC is not applicable.)
Rated input current: changed (Approx.5mA Approx.4mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
(output part)
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (fuse ï‚® overheat, overload protection)
A1SH42P QH42P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
(input part)
Rated input voltage: changed (12VDC is not applicable.)
Rated input current: changed (Approx.5mA Approx.4mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
(output part)
Rated output voltage: not changed
Rated output current: not changed
5) Function: not changed
A1SH42-S1 QH42P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
(input part)
Rated input voltage: not changed
Rated input current: changed (Approx.5mA Approx.4mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
(output part)
Rated output voltage: not changed
Rated output current: not changed
5) Function: changed (fuse ï‚® overheat, overload protection)
A1SH42P-S1 QH42P
1) External wiring: not changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
(input part)
Rated input voltage: not changed
Rated input current: changed (Approx.5mA Approx.4mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
(output part)
Rated output voltage: not changed
Rated output current: not changed
5) Function: not changed
AnS/QnAS series model Q series alternative model
Product Model Model Remarks (restrictions)