117
Torque control by real sensorless vector
control, vector control
4
PARAMETERS
4.5.4 Torque command (Pr. 803 to Pr. 806)
(1) Control block diagram
(2) Torque command (Pr. 804 = "0" (initial value)) by analog input (terminal 1)
Torque command source for torque control can be selected.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
803
Constant power range
torque characteristic
selection
0
0
Constant motor output
command
Select the torque command in the
constant power region by torque
command setting.
1 Constant torque command
804
Torque command
source selection
0
0
Torque command by terminal1 analog input
(Refer to page 288)
1
Torque command by parameter setting (Pr. 805 or Pr. 806)
(-400% to 400%)
3
Torque command by
parameter setting
(Pr. 805 or Pr. 806)
(-400% to 400%)
Torque command with using CC-Link
communication (FR-A7NC)
Setting from the remote resister can be
made. (-400% to 400%)
4 12 bit/16 bit digital input (FR-A7AX)
5
Torque command by
parameter setting
(Pr. 805 or Pr. 806) with
using communication
other than CC-Link
communication
(-400% to 400%)
Torque command with using CC-Link
communication (FR-A7NC)
Setting from the remote resister can be
made. (-327.68% to 327.67%)
6
Torque command with using CC-Link
communication (FR-A7NC)
(-327.68% to 327.67%)
805
Torque command
value (RAM)
1000%
600 to
1400%
Writes the torque command value to the RAM.
On the assumption that 1000% is 0%, the torque command is set by
an offset from 1000%.
806
Torque command
value
(RAM,EEPROM)
1000%
600 to
1400%
Writes the torque command value to the RAM and EEPROM.
On the assumption that 1000% is 0%, the torque command is set by
an offset from 1000%.
⋅ Torque command is given by voltage (current) input to
terminal 1.
⋅ When torque command is input from terminal 1, set "4 or
3" in Pr. 868 Terminal 1 function assignment.
⋅ Torque command by analog input can be calibrated using
calibration parameter C16 (Pr. 919) to C19 (Pr. 920) . (Refer
to page 288 )
Sensorless
Sensorless Vector
Vector
+
-
-
Parameter
(Pr. 805, Pr. 806)
16 bit digital input
(FR-A7AX)
Speed limit input
Analog input
0
1,3,5,6
4
Pr. 804 Torque command
source selection
Torque control
+
Motor
Real sensorless vector control
Vector control
Speed estimator
Encoder
Speed control
(proportional control)
Speed limit value
Speed estimated
value
Speed limit value
Speed estimated
value
Torque command
150%
-100%
(-10V)
0 100%
(+10V)
-150%
Terminal 1
analog input