EasyManua.ls Logo

Mitsubishi FR-A740-00023-EC - USB Communication (Pr. 547, Pr. 548)

Mitsubishi FR-A740-00023-EC
474 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
347
Communication operation and setting
4
PARAMETERS
4.24.8 USB communication (Pr. 547, Pr. 548)
zUSB communication specifications
· When using USB communication, set "3" in Pr. 551 PU mode operation command source selection.
· You can perform parameter setting and monitoring with the FR Configurator. Refer to the instruction manual of the
FR-Configurator for details.
Inverter setup can be easily performed using the FR-Configurator by connecting the inverter and personal
computer with a USB cable.
A personal computer and inverter can be easily connected with one USB cable.
Parameter
Number
Name
Initial Value Setting Range Description
547
USB communication station
number
0 0 to 31 Specify the inverter station number.
548
USB communication check
time interval
9999
0
USB communication is enabled. However, the
inverter will come to an alarm stop (E. USB) if
operation is changed to PU operation mode.
0.1 to 999.8s
Set the interval of communication check time.
If a no-communication state persists for longer
than the permissible time, the inverter will come
to an alarm stop (E.USB).
9999 No communication check
Interfase
Conforms to USB1.1
Transmission
speed:
12Mbps
Connector USB B connector (B receptacle)
Cable
Twisted pair shield cable 5m maximum
Power supply
Self-power supply
Parameters referred to
Pr. 551 PU mode operation command source selection Refer to page 310
USB cable
USB connector
Place a flat-blade screwdriver,
etc. in a slot and push up the
cover to open.
Removal of cover

Table of Contents