164
Frequency setting by external terminals
4.11.3 Input compensation of multi-speed and remote setting (Pr. 28)
4.11.4 Remote setting function (Pr. 59)
* External operation frequency (other than multi-speed) or PU running frequency
(1) Remote setting function
Use Pr. 59 to select whether the remote setting function is used or not and whether the frequency setting storage
function in the remote setting mode is used or not.
When Pr. 59 is set to any of "1 to 3" (remote setting function valid), the functions of the RH, RM and RL signals are
changed to acceleration (RH), deceleration (RM) and clear (RL).
When the remote function is used, the output frequency of the inverter can be compensated for as follows:
External operation
.. Frequency set with RH and RM operation + external operation frequency other than multi-speed
(PU operation frequency when
Pr. 79
= "3" (external, PU combined)) and terminal 4 input.
(When making analog input compensation, set "1" in Pr. 28 Multi-speed input compensation
selection.
When Pr. 28 is set to "0" and acceleration/deceleration is made to reach the set frequency of
the analog voltage input (terminal 2 or terminal 4) by RH/RM, the auxiliary input by terminal 1
becomes invalid.)
PU operation ...........Frequency set by RH/RM operation + PU running frequency
By inputting the frequency setting compensation signal (terminal 1, 2), the speed (frequency) can be
compensated for relative to the multi-speed setting or the speed setting by remote setting function.
Parameter
Number
Name Initial Value Setting Range Description
28
Multi-speed input
compensation selection
0
0 Without compensation
1 With compensation
REMARKS
Select the terminal (terminal 1, 2) used for compensation input voltage (0 to ±5V, 0 to ±10) using Pr. 73 Analog input selection.
When using terminal 1 for compensation input, set "0" (initial value) in Pr. 868 Terminal 1 function assignment.
Parameters referred to
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239 (multi-speed operation) Refer to page 160
Pr. 73 Analog input selection Refer to page 275
Pr. 59 Remote function selection Refer to page 164
Pr. 868 Terminal 1 function assignment Refer to page 274
Even if the operation panel is located away from the enclosure, you can use contact signals to perform
continuous variable-speed operation, without using analog signals.
Parameter
Number
Name Initial Value Setting Range
Description
RH, RM, RL signal
function
Frequency setting
storage function
59 Remote function selection 0
0 Multi-speed setting
1 Remote setting Yes
2 Remote setting No
3 Remote setting
No
(Turning STF/STR off
clears remotely- set
frequency.)
Acceleration
Deceleration
Clear
Inverter
STF
RH
RM 10
2
5
RL
Connection
diagram for remote setting
Forward
rotation
PC
Deceleration
(RM)
Clear (RL)
Acceleration
(RH)
Forward
rotation (STF)
ON
ON
Power supply
ON
0Hz
*
ON
ON
ON
ON
ON
ON
When Pr. 59 = 1
When Pr. 59 = 2, 3
ON
ON
Output frequency
(Hz)
When Pr. 59 = 1, 2
When Pr. 59 = 3
Time

Table of Contents