14
Main circuit terminal specifications
2.2 Main circuit terminal specifications
2.2.1 Specification of main circuit terminal
* Connecting a DC reactor to the 01800
When using the inverter for LD or SLD rating, always connect the supplied DC reactor.
To improve power factor and suppress harmonics with a reactor when using the inverter for ND or HD rating, connect the supplied DC reactor.
It is not necessary to connect the supplied DC reactor for operation other than the above. When not connecting the supplied DC reactor, connect
a supplied jumper across terminals P/+ and P1.
The inverter operates only when either a DC reactor or jumper is connected.
Terminal
Symbol
Terminal Name Description
R/L1,
S/L2,
T/L3
AC power input
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter
(FR-HC and MT-HC) or power regeneration common converter (FR-CV).
U, V, W Inverter output Connect a three-phase squirrel-cage motor.
R1/L11,
S1/L21
Power supply for
control circuit
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
alarm display and alarm output or when using the high power factor
converter (FR-HC
and MT-HC
) or power regeneration common converter
(FR-CV), remove the jumpers from terminals R/L1-R1/L11 and S/L2-S1/
L21 and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1/L11, S1/L21) with the
main circuit power (R/L1, S/L2, T/L3) on. Doing so may damage the
inverter. The circuit should be configured so that the main circuit power (R/
L1, S/L2, T/L3) is also turned off when the power supply for control circuit
(R1/L11, S1/L21) is off.
00380 or less : 60VA, 00470 or more : 80VA
P/+, PR
Brake resistor
connection
(00620 or less)
Remove the jumper from terminals PR-PX (00250 or less) and connect an
optional brake resistor (FR-ABR) across terminals P/+-PR.
For the 00620 or less, connecting the resistor further provides regenerative
braking power.
P/+, N/-
Brake unit
connection
Connect the brake unit (FR-BU2, FR-BU, BU and MT-BU5), power
regeneration common converter (FR-CV), high power factor converter
(FR-HC and MT-HC) or power regeneration converter (MT-RC).
P/+, P1
DC reactor
connection
For the 01160 or less, remove the jumper across terminals P/+ - P1 and
connect the DC reactor. (As a DC reactor is supplied with the 01800 or
more as standard, be sure to connect the DC reactor.*)
PR, PX
Built-in brake circuit
connection
When the jumper is connected across terminals PX-PR (initial status),
the built-in brake circuit is valid. (Provided for the
00250
or less.)
Earth (Ground)
For earthing (grounding) the inverter chassis. Must be earthed
(grounded).
CAUTION
· When connecting a dedicated brake resistor (FR-ABR) and brake unit (FR-BU2, FR-BU, BU) remove jumpers across terminals
PR-PX (00250 or less). For details, refer to page 37 to 42.