4
Inverter and peripheral devices
1.2.1 Peripheral devices
Check the motor capacity of the inverter you purchased. Appropriate peripheral devices must be selected according to
the capacity. Refer to the following list and prepare appropriate peripheral devices:
400V class
Motor Output
(kW)
*1
Applicable Inverter Type
Breaker Selection*2,4 Input Side Magnetic Contactor*3
Reactor connection Reactor connection
without with
without
with
0.4 FR-A740-00023-EC 30AF 5A 30AF 5A S-N10 S-N10
0.75 FR-A740-00038-EC 30AF 5A 30AF 5A S-N10 S-N10
1.5 FR-A740-00052-EC 30AF 10A 30AF 10A S-N10 S-N10
2.2 FR-A740-00083-EC 30AF 10A 30AF 10A S-N10 S-N10
3.7 FR-A740-00126-EC 30AF 20A 30AF 15A S-N10 S-N10
5.5 FR-A740-00170-EC 30AF 30A 30AF 20A S-N20 S-N11, N12
7.5 FR-A740-00250-EC 30AF 30A 30AF 30A S-N20 S-N20
11 FR-A740-00310-EC 50AF 50A 50AF 40A S-N20 S-N20
15 FR-A740-00380-EC 100AF 60A 50AF 50A S-N25 S-N20
18.5 FR-A740-00470-EC 100AF 75A 100AF 60A S-N25 S-N25
22 FR-A740-00620-EC 100AF 100A 100AF 75A S-N35 S-N25
30 FR-A740-00770-EC 225AF 125A 100AF 100A S-N50 S-N50
37 FR-A740-00930-EC 225AF 150A 225AF 125A S-N65 S-N50
45 FR-A740-01160-EC 225AF 175A 225AF 150A S-N80 S-N65
55 FR-A740-01800-EC 225AF 200A 225AF 175A S-N80 S-N80
75 FR-A740-02160-EC 225AF 225A S-N95
90 FR-A740-02600-EC 225AF 225A S-N150
110 FR-A740-03250-EC 225AF 225A S-N180
132 FR-A740-03610-EC 400AF 400A S-N220
160 FR-A740-04320-EC 400AF 400A S-N300
185 FR-A740-04810-EC 400AF 400A S-N300
220 FR-A740-05470-EC 600AF 500A S-N400
250 FR-A740-06100-EC 600AF 600A S-N600
280 FR-A740-06830-EC 600AF 600A S-N600
315 FR-A740-07700-EC 800AF 700A S-N600
355 FR-A740-08660-EC 800AF 800A S-N600
400 FR-A740-09620-EC 1000AF 900A S-N800
450 FR-A740-10940-EC 1000AF 1000A
1000A
Rated product
500 FR-A740-12120-EC 1200AF 1200A
1000A
Rated product
*1 Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 400VAC 50Hz.
*2 Select the MCCB according to the inverter power supply capacity.
Install one MCCB per inverter.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
(Refer to Installation Guideline.)
*3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC
with class AC-3 rated current for the motor rated current.
*4 When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc. Identify
the cause of the trip, then remove the cause and power on the breaker.
MCCB INV
MCCB INV
IM