150
Adjust the output torque of the motor (current)
*1 The rated current differs according to the inverter capacity. Refer to rated specifications (page 426).
(2) Precautions for the FR-A740-01800 or less and FR-A740-02160 or more
If Pr. 570 is set to "0 (SLD) or 1 (LD)" when using FR-A740-01800, specifications of the inverter change to that of the
FR-A740-02160. Setting change of Pr. 570 is made valid after inverter reset and all parameter clear.
For example, when using the FR-A740-01800, setting "0" in Pr. 570 and performing all parameter clear after inverter
reset will change the setting range of Pr. 9 from "0 to 500A" to "0 to 3600A" and the minimum setting increments
from "0.01A" to "0.1A". (Refer to the parameter list for other parameters.)
152
Zero current
detection level
Setting Range
0 to 120% 0 to 150% 0 to 220% 0 to 280%
239
Initial Value
5% 5% 5% 5%
165
Stall prevention
operation level for
restart
Setting Range
0 to 120% 0 to 150% 0 to 220% 0 to 280%
254
Initial Value 110% 120% 150% 200%
271
High-speed setting
maximum current
Setting Range
0 to 120% 0 to 150% 0 to 220% 0 to 280%
361
Initial Value 50% 50% 50% 50%
272
Middle-speed setting
minimum current
Setting Range
0 to 120% 0 to 150% 0 to 220% 0 to 280%
361
Initial Value
100% 100% 100% 100%
279
Brake opening
current
Setting Range
0 to 220% 0 to 220% 0 to 220% 0 to 280%
208
Initial Value
130% 130% 130% 130%
557
Current average value
monitor signal output
reference current
Initial Value
SLD rated
current
*1
LD rated
current
*1
ND rated
current
*1
HD rated
current
*1
378
893
Energy saving
monitor reference
(motor capacity)
Initial Value
SLD value of
applied motor
capacity
*1
LD value of
applied motor
capacity *1
ND value of
applied motor
capacity *1
HD value of
applied motor
capacity *1
267
CAUTION
⋅
When Pr. 570 = "0 or 1", Pr. 260 PWM frequency automatic switchover becomes valid. (Refer to page 272.)
Inverter
Multiple Rating
Setting
Parameter Setting
A740-01800
SLD The inverter operates in the same manner as the FR-A740-02160 or more.
Parameter setting range, minimum setting increments, initial values, etc. change to those
of the 02160 or more. Refer to the parameter list for parameters whose values change.
LD
ND
No change
HD
A740-02160
SLD
No change
LD
ND
HD
Parameter
Number
Name
Pr. 570 Setting
Refer
to
Page
0 1
2
(initial value)
3