281
Frequency/torque setting by analog
input (terminal 1, 2, 4)
4
PARAMETERS
(2) Time constant of analog input (Pr. 74)
Effective for eliminating noise in the frequency setting circuit.
Increase the filter time constant if steady operation cannnot be performed due to noise.
A larger setting results in slower response (The time constant can be set between approximately 10ms to 1s with
the setting of 0 to 8).
(3) Time constant of analog speed command input (Pr. 822, Pr. 832)
Set the time constant of the primary delay filter relative to the external torque command (analog input command)
using Pr. 822 Speed setting filter 1.
Set a large time constant when you want to delay the tracking of the speed command, when the analog input
voltage fluctuates, etc.
When you want to change time constant when switching two motors with one inverter, use the Pr. 832 Speed setting
filter 2.
Pr. 832 Speed setting filter 2 is made valid when the RT signal turns on.
(4) Time constant of analog torque command input (Pr. 826, Pr. 836)
Set the time constant of the primary delay filter relative to the external torque command (analog input command)
using Pr. 826 Torque setting filter 1.
Set a large time constant value when you want to delay the tracking of the torque command, when the analog input
voltage fluctuates, etc.
When you want to change time constant when switching two motors with one inverter, etc., use Pr. 836 Torque setting
filter 2.
Pr. 836 Torque setting filter 2 is made valid when the RT signal turns on.
(5) Offset adjustment of analog speed command
input (Pr. 849)
When speed command by analog input is set, create the
range where the motor remains stop to prevent malfunction
at very low speed.
On the assumption that the Pr. 849 setting 100% as 0, the
offset voltage is offset as follows:
100% < Pr. 849........ positive side
100% > Pr. 849........ negative side
The offset voltage is found by the following formula.
Parameters referred to
Pr. 73 Analog input selection Refer to page 275
Pr. 125, C2 to C4 (Bias and gain of the terminal 2 frequency setting) Refer to page 282
0% 100%
(10V or 5V)
Pr.849 setting
Frequency
command
Speed setting
signal
Slope determined
according to Pr.125
and C2 to C4
Slope does not
change.
0% 200%100%
* According to the Pr. 73 setting
Offset voltage =
Voltage at 100%
(5V or 10V *)
×
Pr. 849
100
[V]
100