285
Frequency/torque setting by analog
input (terminal 1, 2, 4)
4
PARAMETERS
(5) Frequency setting voltage (current) bias/gain adjustment method
(a)Method to adjust any point by application of voltage (current) to across the terminals 2-5 (4-5).
REMARKS
If the frequency meter (indicator) connected to across terminals CA-PC does not indicate just 50Hz, set calibration parameter C0
CA terminal calibration. (Refer to page 251)
DisplayOperation
Analog voltage (current)
value (%) across terminals 2-5
(across terminals 4-5)
Flicker...Parameter setting complete!!
*
*
* The value is nearly 100 (%) in the maximum
position of the potentiometer.
* The value is nearly 100 (%) in the maximum
position of the potentiometer.
CAUTION
After performing the operation in step 6, do not touch until
completion of calibration.
(Adjustment completed)
Press twice to show the next parameter ( ).
C0 to C41
setting
is enabled.
Terminal 2 input Terminal 4 input
Terminal 2 input Terminal 4 input
By turning , you can read another parameter.
Press to return to the indication (step 4).
The parameter
number read
previously appears.
1. Confirmation of the RUN indication and operation
mode indication
The inverter must be at a stop.
The inverter must be in the PU operation mode.
(Using )
2.Press to choose the parameter setting mode.
3.
4.Press to display .
5.
Turn until ( )
appears. Set to
C4 Terminal 2 frequency
setting gain.
6.Press to display the analog voltage (current)
value (%).
7. Apply a 5V (20mA) voltage (current).
(Turn the external potentiometer connected
across terminals 2-5 (across terminals 4-5) to
maximum (any position).)
8.Press to set.