312
Selection of operation mode and operation location
*1 As set in Pr. 338 Communication operation command source and Pr. 339 Communication speed command source. (Refer to page 310)
*2 At occurrence of RS-485 communication error, the inverter cannot be reset from the computer.
*3 Enabled only when stopped by the PU. At a PU stop, PS is displayed on the operation panel. As set in Pr. 75 Reset selection/disconnected PU
detection/PU stop selection. (Refer to page 295)
*4 Some parameters may be write-disabled according to the Pr. 77 Parameter write selection setting and operating status. (Refer to page 298)
*5 Some parameters are write-enabled independently of the operation mode and command source presence/absence. When Pr. 77 = 2, write is
enabled. (Refer to page 65 for the parameter list)Parameter clear is disabled.
*6 When Pr. 550 NET mode operation command source selection = 1 (RS-485 terminals valid) or Pr. 550 NET mode operation command source selection =
9999 and the communication option is not fitted.
*7 When Pr. 550 NET mode operation command source selection = 0 (communication option valid) or Pr. 550 NET mode operation command source selection
= 9999 and the communication option is fitted.
(4) Operation at alarm occurrence
*1 Can be selected using Pr. 75 Reset selection/disconnected PU detection/PU stop selection
*2 Can be selected using Pr. 122 PU communication check time interval, Pr. 336 RS-485 communication check time interval or Pr. 548 USB communication
check time interval.
*3 As controlled by the communication option.
*4 In the PU jog operation mode, operation is always stopped when the PU is disconnected. Whether error (E.PEU) occurrence is allowed or not is
as set in Pr. 75 Reset selection/disconnected PU detection/PU stop selection.
*5 When Pr. 550 NET mode operation command source selection = 1 (RS-485 terminals valid) or Pr. 550 NET mode operation command source selection =
9999 and the communication option is not fitted
*6 When Pr. 550 NET mode operation command source selection = 0 (communication option valid) or Pr. 550 NET mode operation command source selection
= 9999 and the communication option is fitted
Control circuit
external terminals
Inverter reset 
Run command
(start, stop)
×  ××
*1
Frequency setting × × × *1
Alarm
Definition
Operation
Mode
Condition
(
Pr. 551
setting)
PU
Operation
External
Operation
External/PU
Combined
Operation
Mode 1
(Pr. 79 = 3)
External/PU
Combined
Operation Mode
2
(Pr. 79 = 4)
NET Operation
(when RS-485
terminals are
used)
*5
NET Operation
(when
communication
option is used)
*6
Inverter fault
Stop
PU
disconnection
of the PU
connector
2 (PU connector)
Stop/continued *1, 4
Except for 2
Stop/continued *1
Communication
alarm of PU
connector
2 (PU connector)
Stop/
continued
*2
Continued
Stop/continued
*2
Continued
Except for 2
Continued
Communication
alarm of RS-
485 terminals
1 (RS-485 terminals)
Stop/
continued
*2
Continued
Stop/continued
*2
Continued
Except for 1
Continued
Stop/continued
*2
Continued
Communication
alarm of USB
connector
3 (USB connector)
Stop/
continued
*2
Continued
Except for 3
Continued
Communication
alarm of
communication
option
Continued
Stop/continued
*3
Continued
Operation
Location
Condition
(Pr. 551
Setting)
Operation
Mode
Item
PU
Operation
External
Operation
External/PU
Combined
Operation Mode
1
(
Pr. 79
= 3)
External/PU
Combined
Operation
Mode 2
(Pr. 79 = 4)
NET Operation
(when RS-485
terminals are
used)
*6
NET Operation
(when
communication
option is used)
*7
: Enabled, ×: Disabled, : Some are enabled