EasyManua.ls Logo

Mitsubishi FR-A740-00023-EC - Page 359

Mitsubishi FR-A740-00023-EC
474 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
349
Special operation and frequency control
4
PARAMETERS
(1) PID control basic configuration
Pr. 128 = "10, 11" (Deviation value signal input)
Pr. 128 = "20, 21" (Measured value input)
131 PID upper limit 9999
0 to 100%
Set the maximum value. If the feedback value exceeds the
setting, the FUP signal is output. The maximum input (20mA/
5V/10V) of the measured value (terminal 4) is equivalent to
100%.
9999 No function
132 PID lower limit 9999
0 to 100%
Set the minimum value. If the measured value falls below the
setting range, the FDN signal is output. The maximum input
(20mA/5V/10V) of the measured value (terminal 4) is
equivalent to 100%.
9999 No function
133
*1 PID action set point 9999
0 to 100% Used to set the set point for PID control.
9999 Terminal 2 input is the set point.
134
*1 PID differential time 9999
0.01 to
10.00s
For deviation lamp input, time (Td) required for providing only
the manipulated variable for the proportional (P) action. As the
differential time increases, greater response is made to a
deviation change.
9999 No differential control
575
Output interruption
detection time
1s
0 to 3600s
The inverter stops operation if the output frequency after PID
operation remains at less than the Pr. 576 setting for longer
than the time set in Pr. 575.
9999 Without output interruption function
576
Output interruption
detection level
0Hz 0 to 400Hz
Set the frequency at which the output interruption processing
is performed.
577
Output interruption
cancel level
1000% 900 to 1100%
Set the level (Pr. 577 minus 1000%) at which the PID output
interruption function is canceled.
*1 Pr. 129, Pr. 130, Pr. 133 and Pr. 134 can be set during operation. They can also be set independently of the operation mode.
*2 For details, refer to the FR-A700 PLC FUNCTION PROGRAM MANUAL.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
+
-
IM
Deviation signal
Feedback signal (measured value)
Ti S
1
1+
+Td S
Kp
PID operation
To outside
Set point
Inverter circuit
Motor
Terminal 1
0 to 10VDC
(0 to 5V)
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
Manipulated
variable
+
-
IM
Ti S
Kp 1+ +Td S
1
PID operation
Pr. 133 or
terminal 2
Set point
Inverter circuit
Motor
Feedback signal (measured value)
Terminal 4
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
Manipulated
variable
0 to 5VDC
(0 to 10V, 4 to 20mA)
4 to 20mADC (0 to 5V, 0 to 10V)

Table of Contents

Related product manuals