5
REDUNDANT SYSTEM FUNCTIONS
5.5 Tracking Function
5.5.4 Tracking Data Settings
5 - 82
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
TRACKING CABLE
4
PROCEDURE FOR
STARTING UP A
REDUNDANT SYSTEM
5
REDUNDANT SYSTEM
FUNCTIONS
6
REDUNDANT SYSTEM
NETWORKS
7
PROGRAMMING
CAUTIONS
8
TROUBLESHOOTING
5.5.4 Tracking Data Settings
Make the tracking data settings at Tracking settings in Redundant parameter in GX
Developer.
If no tracking settings are made by the user, Tracking device settings will be set to "Internal
device block setting" (default) and tracking will be executed based on "Default Tracking
Range" in Table5.44 in Section 5.5.3 (1).
Diagram 5.49 Tracking Setting Screen
Table5.48 Tracking Setting Items and Ranges
Item Range Default Reference
1 Tracking device setting
• Internal device block setting
• Device detail settings
Internal device block setting
Section
5.5.3
2 Signal flow memory tracking setting
• No tracking
• Enable tracking of signal flow memory
No tracking
Section
5.5.3
3 Tracking block No. • 1 to 64 1
Section
5.5.5
4
Device range Settings
*1
Device
• Table5.44 Tracking Range Set by User
Table5.44 Default Tracking
Range
Section
5.5.3
Points / Start
Start / End
5 Tracking characteristics setting
• Synchronized tracking mode
• Program priority mode
Synchronized tracking mode
Section
5.5.7
6 Do auto forward Tracking block No. 1
• Do auto forward Tracking block No. 1
• Do not auto forward Tracking block No. 1
Do auto forward Tracking
block No. 1
Section
5.5.5
7
File register
file settings
*2
Target
memory
• Memory card (SRAM)
• Standard RAM
––
File name
Sets tracking file register file name
• Up to 8 half-width characters
• Cannot include the following characters:
\ / : ; * ? < > | += [ ] . ,
––
1)
6)
7)
2)
3)
5)
4)