3 - 2
3.3 Connecting and Disconnecting a Tracking Cable
3
TRACKING CABLE
3.3 Connecting and Disconnecting a Tracking Cable
(1) Cautions when Connecting a Tracking Cable
Be careful not to step on the tracking cable.
When laying tracking cables, secure a minimum bending radius of 27.6 mm or
more.
If the bending radius is less than 27.6 mm, a malfunction may occur due
characteristic deterioration, wire breakage, etc.
POINT
1. Always power OFF the standby system or set the RESET/L.CLR switch of the
standby system CPU module to RESET before connecting or disconnecting
the tracking cable.
2. To connect or disconnect the tracking cable, hold it by the cable connector.
Diagram 3.1 Minimum Bending Radius of a Tracking Cable
Tracking cable
R (Bending Radius)
When connected: 27.6 (1.09) or more
89.3 (3.52)
35.0 (1.38)
6.9 (0.27)
73.0 (2.87)
Unit: mm (inch)