2 - 18
2.4 System Configuration Cautions
2
SYSTEM CONFIGURATION
2.4 System Configuration Cautions
(1) Extension base unit
The extension base unit cannot be connected to the main base unit where the
Redundant CPU whose first 5 digits of serial No. is "09011" or earlier is mounted.
If connected, a stop error "BASE LAY ERROR (error code: 2010)" occurs.
When connecting the extension base unit, there are following restrictions.
Use Redundant CPUs whose first 5 digits of serial No. are "09012" or later for
both systems.
Connnect a redundant type extension base unit as the first extension stage. As
the second and later stages, redundant power extension base units only can be
used.
Only one redundant type extension base unit can be used per system.
Connect IN connector (IN1 and IN2) of the redundant type extension base unit to
OUT connector of the main base unit.
Connect OUT connector of the redundant type extension base unit to IN
connector of the redundant power extension base unit.
Use the same main base unit models in systems A and B.
Configuration of multiple CPU system is not allowed.
Do not power OFF or reset the control system in Separate mode.
Do not perform boot operation of a Redundant CPU whose first 5 digits of serial
No. is "09011" or earlier, using a memory card storing network parameters for
Ethernet and CC-Link configurations on an extension base unit.
Do not disconnect the extension cable while the power supply module mounted
on the main base unit is ON.
Any dedicated instructions cannot be used to intelligent function modules on
extension base units. ( Section 7.1 (8))
Any interrupt pointer caused by an interrupt from an intelligent function module
on an extension base unit cannot be used. ( Section 7.5 (4))
Connect extension cables so that an overall cable distance
*1
does not exceed
13.2 m (43.31 feet).
* 1: To calculate an overall cable distance, use the longer length for the two extension cables
connecting between the system A or B main base unit and the redundant type extension base unit
System A
System B
System A extension cable:
1.5 m(4.92 feet)
Example) System A extension cable...1.5 m(4.92 feet)
System B extension cable...3 m(9.84 feet)
Extension cable: 2 m(6.56 feet)
Extension cable: 5 m(16.40 feet)
System B extension cable: 3 m(9.84 feet)
3+2+5=10 m(32.81 feet) 13.2 m(43.31 feet)