App - 9
Appendix 3 Comparison of QnPHCPU and QnPRHCPU
APPENDICES
Appendix 3 Comparison of QnPHCPU and QnPRHCPU
A comparison of QnPHCPU and QnPRHCPU is shown in Table App.6.
Table App.6 Comparison of QnPHCPU and QnPRHCPU
Item QnPRHCPU QnPHCPU
Performance
Scan Time
Scan time is increased by the tracking time.
Internal device 48 k word setting time
Synchronized tracking mode: 41 ms
Program priority mode: 21 ms
-
System
Configuration
Maximum Number of
Modules Mounted on Main/
Extension Base Unit
<<First 5 digits of serial No. is "09011" or earlier>>
11 modules (Main base unit only)
Modules which are not duplicated are mounted
to MELECNET/H remote I/O station (Number of
mountable modules on remote I/O station: 64
modules per station)
<<First 5 digits of serial No. is "09012" or later>>
Up to 63 modules
(Main base unit + extension base unit: 7 stages)
64 Slots (Main base unit + Extension
base unit: 7 stages)

Table of Contents