App - 11
Appendix 3 Comparison of QnPHCPU and QnPRHCPU
APPENDICES
Table App.6 Comparison of QnPHCPU and QnPRHCPU (Continued)
Item QnPRHCPU QnPHCPU
System
Configuration
Multi CPU System N/A Applicable
Single CPU System Applicable (Debug mode only) Applicable
GOT
Connection
Type
Bus
Connection
N/A Applicable
CPU Direct
Connection
Applicable (Communication with the CPU module
connected to the GOT only)
Applicable
Computer Link
Connection
N/A Applicable
Ethernet
Connection
Applicable Applicable
CC-Link IE
Controller
Network
Connection
Applicable (N/A for extension base unit) Applicable
MELSECNET/
H PLC to PLC
Network
Connection
Applicable (N/A for extension base unit) Applicable
CC-Link
Connection
Applicable Applicable
MELSECNET/
H Remote I/O
Station
Connection
Applicable (N/A for extension base unit)
Applicable
Mounting I/O module or
network module on slot 0
Disabled (Slot 1 becomes I/O number "0".)
Mount I/O modules and network modules on slots
1 and later.
Enabled
Restriction on the
applicable intelligent
function modules
Applied
The Ethernet modules and MELSECNET/H
module of serial No. "06052" or later are applicable.
Not applied
Programming
Too l
GX Developer Version 8.18U or later is applicable. Version 7 or later is applicable.
PX Developer Version 1.06G or later is applicable Version 1.00A or later is applicable.
Program
Instruction restriction Instructions listed in Table App.7 are inapplicable. -
Low-speed Execution Type
Program
N/A Applicable