SYSTEM CONFIGURATION
2.1 System Configuration
2 - 5
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
TRACKING CABLE
4
PROCEDURE FOR
STARTING UP A
REDUNDANT SYSTEM
5
REDUNDANT SYSTEM
FUNCTIONS
6
REDUNDANT SYSTEM
NETWORKS
7
PROGRAMMING
CAUTIONS
8
TROUBLESHOOTING
(3) Communication via CC-Link IE Controller Network or MELSECNET/H
PLC to PLC Network
(a) Connecting Redundant System to CC-Link IE Controller Network,
MELSECNET/H, and MELSECNET/10 PLC to PLC Network
A redundant system can communicate with Q series CPU modules connected to
CC-Link IE Controller Network or MELSECNET/H PLC to PLC network.
The system can also connect to MELSECNET/10 PLC to PLC network and
communicate with Q series, QnA series, and A series CPU modules.
(b) Pairing Settings and Relevant CPU Modules
Pairing settings must be made using the control station network parameters when
connecting a redundant system to CC-Link IE Controller Network, MELSECNET/
H, or MELSECNET/10.
The following CPU modules include the network parameters for paring settings.
Redundant CPU
*1
High Performance model QCPU
*1
Process CPU
*1
Basic model QCPU
*1
Universal model QCPU
*1
Q4ARCPUs
*1 *2 *3
When connecting a redundant system to a network, set any of the above CPU
modules as the control station.
CPU modules other than above can be set as the normal station only.
Refer to the following manuals, for details on pairing settings for CC-Link IE
Controller Network, MELSECNET/H, and MELSECNET/10 PLC to PLC networks.
CC-Link IE Controller Network Reference Manual
Q Corresponding MELSECNET/H Network System Reference Manual (PLC
to PLC network)
QnA/Q4AR Corresponding MELSECNET/10 Network System Reference
Manual